BRE 365 soakaway calculation method

This calculator implements the published BRE 365 volume-balance approach for a rectangular infiltration device receiving clean impermeable-roof runoff. It uses Irish rainfall depths and your site measurements. A calculation pack is an aid to professional review; it is not a certificate of compliance.

Infiltration from a trial pit

For each of three repeats, f = V75–25 / (Ap50 × elapsed seconds). The lost volume is half the maximum water depth times the pit plan area. Ap50 includes the pit base and sidewalls to half the actual maximum water depth. The lowest repeat rate is adopted, then divided by the selected safety factor.

A measured-rate entry must come from a suitable site test report. The tool cannot check how a test was carried out or infer permeability from soil descriptions.

Storage and storm duration

For every returned duration, inflow is roof area × climate-adjusted rainfall depth. Potential outflow is design infiltration rate × duration × sidewall area at half effective depth. The device base is excluded from this design outflow area. Required storage is the largest positive inflow minus outflow across the checked durations.

The Met Éireann service supplies the selected 10, 30 or 100-year rainfall depths, including available multi-day durations up to seven days. The longest available duration controlling the result is flagged for further assessment.

Geometry and drawdown

Usable storage is length × width × effective depth × void fraction. Effective depth is the storage depth below the incoming pipe invert. The half-volume check conservatively uses half the full usable capacity divided by the design outflow rate, and compares that time with 24 hours.

Automatic sizing searches a domestic envelope of up to 15 m length, 3 m width and 2 m effective depth. It offers no size when storage, drawdown and any entered garden envelope cannot all be met. Manufacturer modules, structural loading and construction details remain to be checked.

Assumptions and site review

Defaults are 100-year rainfall, +20% climate change, infiltration safety factor 2, impermeable-roof runoff coefficient 1, and either 95% crate or 30% stone voids. These are stated assumptions, not universal BRE or authority requirements. Set the allowances your project requires and confirm actual product voids.

The site screens use 5 m from foundations, 3 m from adjoining boundaries and 1 m above highest seasonal groundwater. The optional garden check assumes a clear rectangle measured from the house foundation to the rear boundary, with adjoining boundaries on both sides. It reserves 5 m at the house, 3 m at the rear and 3 m at each side, then checks both orientations of the device plus the selected excavation allowance (initially 0.3 m each side). Unknown site values stay unconfirmed. These screens do not locate neighbouring buildings, roads, sewers, watercourses, pollution, stability, utilities or obstacles; road boundaries can require 5 m. Confirm the actual excavation dimensions and every local authority condition. A qualified designer must check the full current Digest and project requirements before construction.

References

Read the soakaway sizing and planning guide for an explanation of inputs, material options and the €10 pack.